18 November 2026 by

KNX commissioning mistakes are rarely exotic. Five of the most avoidable are duplicate addresses, a line loaded to its limit with no spare supply, a coupler that is not set up as the plan assumes, bus and mains cable sharing a box, and no backup of the ETS project. This post explains each one and what to ask your integrator so that it does not reach your house.

What is commissioning?

Commissioning is the stage where the wired system becomes a working one. A certified integrator programs the devices in ETS, the KNX engineering software, loads the project into them, tests every function and hands the system over. Because every KNX device carries its own logic, there is no central controller that the whole building depends on, and also no single place where a mistake is caught for you. Careful checking has to be part of the job.

This post is about practice, not about any one project. Treat it as a list of questions for your own integrator.

1. Duplicate physical addresses

Every device on a KNX installation has a physical address that identifies it on the bus, based on its area, line and position. Two devices with the same address on the same line cause confusing faults: a device that cannot be programmed, or one that answers when another was meant to. The usual cause is a copied device, or a spare device that is brought in later and programmed with an address already used.

Ask for: a list of physical addresses in the handover pack, and a statement that ETS shows no duplicates.

2. A line loaded to its limit with no spare supply

A KNX line has limits: up to 64 devices with a 640 mA power supply, up to 350 m of cable from the supply to the furthest device, up to 700 m between any two devices, and up to 1,000 m in total. A line that is full on day one has no room for the next room the owner adds. The device count also depends on the current each device draws, and some panels and gateways draw more than a simple input.

Ask for: the plan of the lines, with the devices on each, the supply for each, and at least a quarter of each line's capacity left free. Our KNX cable guide sets out the numbers.

3. A line coupler that does not match the plan

A line coupler joins one line to the next and filters traffic, so that messages for one line stay on that line. This is good for the bus, and it only works as intended if the coupler is set up to match the group addresses in use. A coupler that is set to pass too much defeats the purpose. One that is set to pass too little can stop a switch on one line from reaching an actuator on another.

Ask for: a test that a switch on one line operates an actuator on a different line, written into the commissioning checklist.

4. Bus and mains cable in one junction box

The KNX bus is a low-voltage circuit at 30 V DC SELV, and mains is not. A box that carries both leaves a safety-critical separation to whoever opens it next. How the two are separated in conduits and wall boxes depends on the electrical code that applies to your project and on the integrator's method, so ask for it to be written down before the wiring starts.

  • Keep bus and mains cable in separate conduits where the installer's method calls for it.
  • Label both ends of each bus cable with the line number.
  • Use a differently coloured sheath for any second 30 V DC auxiliary supply cable, so the two are not mixed up.

Our post on KNX cable covers the cable type and what the datasheet should say.

5. No backup of the ETS project

The ETS project file holds the design of the whole system: which device sits where, which group address does what, and the parameters in every device. Without it, a change years later starts from the devices alone, and parameters are not always readable back from them. A project that exists on one laptop is a risk for the life of the house.

Ask for: the ETS project file in the handover pack, a copy kept by the owner, and a clear statement of who owns it. A system is only finished when a stranger can understand it.

A one-page handover list

  1. Physical address list, with no duplicates.
  2. Line plan with devices, supplies and spare capacity.
  3. Coupler test across lines.
  4. Cable type and separation from mains, written down.
  5. ETS project file, backed up, with the owner named.
  6. Names of who commissions and who services the system.

None of these costs much when it is done during commissioning. Each is expensive to fix afterwards.

Questions people ask

What is KNX commissioning?

It is the stage where a certified integrator programs the devices in ETS, loads the project, tests every function and hands the system over to the owner.

Who should own the ETS project file?

The owner should receive it in the handover pack and keep a copy. Without it, later changes are slower and some device settings cannot be recovered.

How many devices can one KNX line take?

Up to 64 devices with a 640 mA power supply, within the cable limits, and it depends on the current each device draws. Leave spare capacity for later additions.

Planning a KNX project? Start with our KNX guide for India, or talk to our team.

Sources checked on 17 November 2026

  1. Morion Automation, KNX in India, for how KNX systems are programmed in ETS by a certified integrator and have no central controller.
  2. Morion Automation, KNX cable in India, for the line limits, the 30 V DC SELV bus and the use of line couplers.
  3. KNX Association, What is KNX, for KNX as an open standard.